Resumo (PT):
Abstract (EN):
— The main objective of this work is a technical
and economic analysis of a flooded evaporator in a vapour
compression refrigerant cycle using R134a as working fluid.
To achieve this goal, it was used a simulation software, the
Pack Calculation Pro 4.2. A comparison of the annual energy
consumption of the refrigeration system with a flooded
evaporator was carried out having as reference the same
system with a dry evaporator. In this study are analysed the
advantages and disadvantages of using the two types of
evaporators, the flooded and dry one, in situations of presence
of overheating for the dry evaporator and the presence of the
pump in the flooded evaporator. It was concluded that the
advantage in the implementation of flooded evaporator is
directly proportional to the degree of overheating at the exit
of the dry evaporator
Idioma:
Inglês
Tipo (Avaliação Docente):
Científica
Nº de páginas:
6