Abstract (EN):
A number of factors influence the performance of an ejector, e.g. working fluid, geometry and operating conditions. In the present work, six low-environmental-impact working fluids were evaluated for their use in an ejector cooling system running on low-temperature thermal energy. The numerical analysis was based on a model applying the 1D constant-pressure mixing theory. Ejector performance was assessed for the temperatures of the generator, evaporator and condenser in the range of 80-120 degrees C, 5-15 degrees C and 25-40 degrees C, respectively. The results indicated that owing to its high coefficient of performance and moderate operating pressures throughout the entire ejector cycle, isobutane is a good choice for a refrigerant. The area ratio required for running the ejector in critical mode, under changing operating conditions, varied in a significant range regardless of the selected refrigerant. This clearly indicates the importance of a variable geometry ejector design to strengthen the position of ejector cooling systems among other refrigeration technologies.