Saltar para:
Logótipo
Comuta visibilidade da coluna esquerda
Você está em: Início > Publicações > Visualização > A simple ESR identification methodology for Electrolytic Capacitors conditon monitoring

A simple ESR identification methodology for Electrolytic Capacitors conditon monitoring

Título
A simple ESR identification methodology for Electrolytic Capacitors conditon monitoring
Tipo
Artigo em Livro de Atas de Conferência Internacional
Ano
2007
Autores
A. Vicente T. leite
(Autor)
FEUP
Henrique J. A. Teixeira
(Autor)
FEUP
Ver página pessoal Sem permissões para visualizar e-mail institucional Pesquisar Publicações do Participante Sem AUTHENTICUS Sem ORCID
A. J. Marques Cardoso
(Autor)
Outra
A pessoa não pertence à instituição. A pessoa não pertence à instituição. A pessoa não pertence à instituição. Sem AUTHENTICUS Sem ORCID
Rui Esteves Araújo
(Autor)
FEUP
Ata de Conferência Internacional
Páginas: 75-84
20th International Congress on Condition Monitoring and Diagnostic Engineering Management, COMADEM’07
Faro (Portugal), 13 a 15 de Junho de 2007
Classificação Científica
FOS: Ciências da engenharia e tecnologias > Engenharia electrotécnica, electrónica e informática
CORDIS: Ciências Tecnológicas > Engenharia > Engenharia electrotécnica
Outras Informações
ID Authenticus: P-010-VGF
Abstract (EN): Electrolytic capacitors are usually used in power electronic systems for smoothing, energy storage or filtering. They have the best overall performance for these objectives being a critical element in the design of these systems, in several applications, with different requirements. But, infortunately, in most cases, they are the most life-limiting device. The expected life of electrolytic capacitors depends on their internal temperature and is determined by the ratio of the electrolyte solution evaporation used in their fabrication. The deterioration caused by this evaporation is reflected in electrical parameters, mainly the equivalent series resistance (ESR). As the volume of the electrolyte decreases, ESR increases and capacitance decreases. Additionally, the increase in ESR has a positive feedback effect since it leads the temperature to increase and this in turn leads to further evaporation of the electrolyte leading to the ESR increase and so forth. This paper presents a simple ESR identification methodology for electrolytic capacitors condition monitoring in view of preventive maintenance to signal the need of maintenance and or replacement. The identification methodology is based on a simple continuous-time model and some recursive prediction error methods, namely, Kalman filter, gradient and orgetting factor approaches. Simulation and experimental data acquired from a step down converter were used with these algorithms. The identification methodology is also suitable for different power converter topologies.
Idioma: Inglês
Tipo (Avaliação Docente): Científica
Contacto: avtl@ipb.pt
Nº de páginas: 10
Tipo de Licença: Clique para ver a licença CC BY-NC
Documentos
Nome do Ficheiro Descrição Tamanho
avtl_COMADEM07_82-1 193.44 KB
Recomendar Página Voltar ao Topo
Copyright 1996-2025 © Centro de Desporto da Universidade do Porto I Termos e Condições I Acessibilidade I Índice A-Z
Página gerada em: 2025-10-24 às 08:47:50 | Política de Privacidade | Política de Proteção de Dados Pessoais | Denúncias | Livro Amarelo Eletrónico