Evaluating the Performance of External Fault Ride-Through Solutions used in Wind Farms with Fixed Speed Induction Generators when Facing Unbalanced Faults

Title
Evaluating the Performance of External Fault Ride-Through Solutions used in Wind Farms with Fixed Speed Induction Generators when Facing Unbalanced Faults
Type
Article in International Conference Proceedings Book
Year
2009
Authors
Resende, FO
(Author)
Other
The person does not belong to the institution. The person does not belong to the institution. The person does not belong to the institution. View Authenticus page Without ORCID
João Peças Lopes
(Author)
FEUP
View Personal Page You do not have permissions to view the institutional email. Search for Participant Publications View Authenticus page View ORCID page
Conference proceedings International
Pages: 626-631
Bucharest PowerTech Conference
Bucharest, ROMANIA, JUN 28-JUL 02, 2009
Indexing
Other information
Authenticus ID: P-003-SR3
Abstract (EN): The continuous growth of wind energy integration on electrical networks has led many utilities to impose fault ride-through capability to wind farms. This means that wind turbines must remain connected to the system during severe fault occurrence. Regarding the existing wind farms equipped with fixed speed induction generators directly connected to the grid, fault ride-through capability is commonly assisted with dynamic compensation devices, such as DSTATCOM units. These power electronic devices are controlled for voltage regulation purposes and behave like a balanced three-phase voltage source converter since commonly used control techniques are based only on the positive sequence of both voltage and current measured at its connection point. These control techniques are suitable only when compensation devices are operated under balanced conditions and therefore its performance when facing unbalanced faults needs to be evaluated. This paper tackles with this subject and the results obtained through numerical simulations demonstrate that over voltages can arise on non faulty phases leading to the wind farm disconnection.
Language: English
Type (Professor's evaluation): Scientific
No. of pages: 6
Documents
We could not find any documents associated to the publication.
Related Publications

Of the same authors

Using low voltage MicroGrids for service restoration (2007)
Article in International Scientific Journal
Moreira, CL; Resende, FO; Pecas A P Lopes
Service restoration on distribution systems using Multi-MicroGrids (2011)
Article in International Scientific Journal
Resende, FO; Gil, NJ; João Peças Lopes
Optimal management of battery charging of electric vehicles: A new microgrid feature (2011)
Article in International Conference Proceedings Book
Karnama, A; Resende, FO; João Peças Lopes
Management and control systems for large scale integration of renewable energy sources into the electrical networks (2011)
Article in International Conference Proceedings Book
Resende, FO; João Peças Lopes
Development of dynamic equivalents for MicroGrids using system identification theory (2007)
Article in International Conference Proceedings Book
Resende, FO; João Peças Lopes

See all (6)